50-80Kva Efficiency Vs. Load (Typical, No Transformer); 50-80Kva Thermal Loss Vs. Load (Typical, No Transformer) - Toshiba 4400 Series Installation And Operation Manual

Table of Contents

Advertisement

4400 SPECIFICATIONS: 50–80kVA w/ External Battery Backup
Specification
RS-232 Inrterface
Optional – Intelligent Monitoring
Optional – Remote Status Alarm
Panel (RSAP)
ADDITIONAL FEATURES
Optional Matching Battery Cabinets
Optional Matching MBS/PDU Cabinet
OTHER
Warranty (yr.)
Certifications
2 - Minimum front clearance for unobstructed airflow is 20 inches. However, minimum front clearance when
physically accessing the UPS must be at least the width of the front door of the UPS, or per NEC 110.34(A)
(36 i n./900 mm) and local requirements, whichever is greater.
3 - Approximate weights for dual-input units. Actual weights may vary depending on exact UPS configu-
ration.
11.9
50–80kVA Efficiency vs. Load (Typical, No Transformer)
UPS
50kVA
50kVA + 1 Xfmr.
50kVA + 2 Xfmr.
80kVA
80kVA + 1 Xfmr
* Subject to change without notice.
11.10 50–80kVA Thermal Loss vs. Load (Typical, No Transformer)
UPS
50kVA
50kVA + 1 Xfmr.
50kVA + 2 Xfmr.
80kVA
80kVA + 1 Xfmr
* Subject to change without notice.
4400 Series Installation and Operation Manual – 64527-006
50kVA
UL 1778, CUL, NEC (NFPS-70), CE, IBC, CBC, ANSI C62.41 (IEEE 587),
Nema/PET-1993, OSHA, ISO9000, ISO 14001:2004.
% EFFICIENCY AT VARIOUS LOADS*
Percent Full Load
25%
50%
88.8%
90.9%
85.8%
87.9%
82.8%
84.9%
88.8%
90.9%
85.8%
87.9%
THERMAL LOSS AT VARIOUS LOADS*
BTU/hr. Loss at Percent Full Load
0%
25%
3412
4856
4095
6369
4095
7991
5459
7770
6824
10,190
80kVA
Yes
Yes – RemotEye 4
Yes
Yes
Yes
3 Years
75%
100%
91.0%
91.0%
88.0%
88.0%
85.0%
85.0%
91.0%
91.0%
88.0%
88.0%
50%
75%
100%
7695
11,389
15,186
10,578
15,703
20,938
13,665
20,322
27,096
12,312
18,223
24,297
16,925
25,125
33,501
65