Input
Input Current (Input Currrent + Charging Current) at Full Load (A)
Voltage
15 kVA
230/133V
39 (43)
240/139V
37 (41)
380/220V
24 (26)
400/227V
22 (25)
415/240V
22 (24)
480/277V
19 (21)
600/347V
15 (17)
D.8 – Output Transformer Current for Given Output Voltage
TABLE D.8 – OUTPUT TRANSFORMER CURRENT AT GIVEN OUTPUT VOLTAGE
Output
Voltage
15 kVA
208/120V
42
220/127V
39
230/133V
38
240/139V
36
380/220V
23
400/227V
22
415/240V
21
480/277V
18
600/347V
14
116
20 kVA
25 kVA
52 (56)
65 (69)
50 (54)
62 (66)
31 (34)
39 (42)
30 (32)
37 (39)
29 (31)
36 (38)
25 (27)
31 (33A
20 (22)
25 (27)
Output Current at Full Load (A)
20 kVA
25 kVA
56
69
52
66
50
63
48
60
30
38
29
36
28
35
24
30
19
24
4400 Series Installation and Operation Manual – 64527-006
30 kVA
50 kVA
78 (82)
130 (138)
75 (79)
124 (132)
47 (50)
78 (84)
45 (47)
75 (79)
43 (46)
72 (77)
37 (39)
62 (66)
30 (32)
50 (53)
30 kVA
50 kVA
83
139
79
131
75
126
72
120
46
76
43
72
42
70
36
60
29
48
80 kVA
207 (222)
199 (213)
126 (134)
119 (128)
115 (123)
99 (106)
80 (85)
80 kVA
222
210
201
192
122
115
111
96
77