50–80kVA Specifications – w/ External Battery Backup
4400 SPECIFICATIONS: 50–80kVA w/ External Battery Backup
Specification
GENERAL
Model Number
X – External Batt. Backup
Capacity Output
Topology
INPUT
Voltage (V)
Current (Nominal) (A)
Current (Max) (A)
Current Limit (%)
Current THD (%)
Frequency (Hz) [and range]
Input Power Factor (PF) @ full load
Walk-in Function (sec)
Cold Start (0-100% load) (sec)
BYPASS
Voltage (V)
Frequency (Hz)
Bypass Overload @ 125% Load
Bypass Overload @ 150% Load
Bypass Overload @ 1000% Load
Automatic Retransfer (Max load % for
Retansfer)
OUTPUT
1 - Requires adjustment of factory/service adjustable parameters.
62
50kVA
4400x3x500xA
50kVA (45kW)
Double conversion all-IGBT UPS
Nominal (Xfmr.) Input Voltage +10% to -15% (Intermittently to -30% at 70%
load
), 3P/4W +GND or 3P/3W + GND
1
Key
Transformer Voltage
A
200V Iso Xfmr
B
208V Iso Xfmr
C
220V Iso Xfmr
D
230V Iso Xfmr
E
240V Iso Xfmr
F
208/120V (No Xfmr)
G
220/127V Auto-Xfmr
H
380/220V Auto-Xfmr
I
400/230V Auto-Xfmr
J
415/240V Auto-Xfmr
K
480/277V Auto-Xfmr
139 A
148 A
20% to 100% over 5 sec.
25 sec. from cold start
Nominal Output Voltage, 3P/4W +GND or 3P/3W + GND
See Input Voltage Transformer Key
10 min. @ 125% Load
2 min. @ 150% Load
1 cycle @ 1000% Load
4400 Series Installation and Operation Manual – 64527-006
80kVA
4400x3x800xA
80 kVA (72kW)
Key
Transformer Voltage
M
380V Iso Xfmr
N
400V Iso Xfmr
P
415V Iso Xfmr
Q
230/133V Auto-Xfmr
R
240/139V Auto-Xfmr
S
480V Iso Xfmr
T
(Undefined)
U
600/347V Auto-Xfmr
V
600V Iso Xfmr
X
Not Used
Z
200/115V Auto-Xfmr
222 A
238 A
125% of Rated load
< 5%
50/60 Hz ± 5 Hz
>0.98
(not selectable)
50/60 Hz ±5%
Yes