Installation Planning Guide for 15-80kVA UPS
Standard System: 208/120V Input, 208/120V Output
UPS kVA/ kW
Rating
15 kVA/ 13.5 kW
20.12 x 37.4 x 65.06
20 kVA/ 22.5 kW
20.12 x 37.4 x 65.06
25 kVA/ 22.5 kW
20.12 x 37.4 x 65.06
30 kVA/ 27 kW
20.12 x 37.4 x 65.06
50 kVA/ 45 kW
32.1 x 37.2 x 73.8
80 kVA/ 72 kW
32.1 x 37.2 x 73.6
Primary AC Input (208/120V 3-Phase / 4-Wire)
Maximum Input Power Demand
kVA
PF
Amps
15
>0.99
42 (46)
20
>0.99
55 (60)
25
>0.99
69 (74)
30
>0.99
83 (88)
50
>0.99
139 (148)
80
>0.99
222 (238)
Bypass AC Input (208/120V 3-Phase / 4-Wire)
Maximum Input Power Demand
kVA
PF
Amps
15
>0.99
42
20
>0.99
56
25
>0.99
69
30
>0.99
83
50
>0.99
139
80
>0.99
222
Battery Capacity Required
Maximum Discharge
for Full Load Output
at Full Load Output
kVA
kWB
15
15
20
20
25
25
30
30
50
50
80
80
1 – External overcurrent overprotection not needed if battery cabinet(s) are each equipped with an appropriate internal circuit breaker
2 – External feeder cables may change depending on number of battery cabinets placed in parallel.
Rated Output Power
kVA
PF
Amps
15
0.9
42
20
0.9
56
25
0.9
69
30
0.9
83
50
0.9
139
80
0.9
222
112
Rev. 1.4
TOSHIBA
General Mechanical Information
Dimensions
Weight
(W x D x H)
Bare (w/ Int Batt.)
Inches
Lbs.
725 (1015)
730 (1020)
750 (1035)
760 (1045)
965 (1920)
1550 (N/A)
Suggested External
Suggested Minimum Feeder Wire Size
Feeder Breaker
Amps
AWG or kcmil at 75º C Temp. Rating
60
(1) x 4 AWG / (1) x 2 AWG
80 A
(1) x 3 AWG / (1) x 2 AWG
100 A
(1) x 2 AWG / (1) x 2 AWG
110 A
(1) x 2 AWG / (1) x 2 AWG
200 A
(1) x 4/0 / (1) 250 kcmil
300 A
(1) x 500 kcmil / (2) 500 kcmil
Suggested External
Suggested Minimum Feeder Wire Size
Feeder Breaker
Amps
AWG or kcmil at 75º C Temp. Rating
60 A
(1) x 4 AWG / (1) x 2 AWG
80 A
(1) x 3 AWG / (1) x 2 AWG
90 A
(1) x 2 AWG / (1) x 2 AWG
110 A
(1) x 2 AWG / (1) x 2 AWG
200 A
(1) x 4/0 / (1) 250 kcmil
300 A
(1) x 500 kcmil / (2) 500 kcmil
Battery Backup (288VDC Nominal)
Suggested External
Feeder Breaker
Amps DC
Amps
65 A
70 A
87 A
90 A
109 A
110 A
130 A
150 A
217 A
225 A
347 A
350 A
AC Output (208/120V 3-Phase / 4-Wire)
Suggested External
Suggested Minimum Feeder Wire Size
Feeder Breaker
Amps
AWG or kcmil at 75º C Temp. Rating
60 A
(1) x 4 AWG / (1) x 2 AWG
80 A
(1) x 3 AWG / (1) x 2 AWG
90 A
(1) x 2 AWG / (1) x 2 AWG
110 A
(1) x 2 AWG / (1) x 2 AWG
200 A
(1) x 4/0 / (1) 250 kcmil
300 A
(1) x 500 kcmil / (2) 500 kcmil
4400 Series Installation and Operation Manual – 64527-006
Page 1 of 2
4400 UPS
Approximate Full-
Mechanical Clearance for Ventilation
Load Heat Loss
and Maintenance Access
kBtu/Hr
4.6
Top:
16 in
6.1
(406 mm)
7.6
9.1
15.2
24.3
Suggested Maximum Feeder Length
Per Phase / Neutral
For Min. Wire Size in Steel Conduit
Suggested Maximum Feeder Length
Per Phase / Neutral
For Min. Wire Size in Steel Conduit
Suggested Minimum Feeder
1
Wire Size Per Polarity
AWG or kcmil at 75º C Temp. Rating
6 AWG – 4 AWG
4 AWG – 3 AWG
2 AWG
2 AWG
4/0 – 250 kcmil
500 kcmil – (2) x 2/0
Suggested Maximum Feeder Length
Per Phase / Neutral
For Min. Wire Size in Steel Conduit
4400-IPG-208/120v-208/120V
Front:
Bottom/
36 in
Sides/
(900 mm)
Back:
0 in.
(0 mm)
Feet
380
380
380
380
380
380
Feet
380
380
380
380
380
380
Suggested Maximum
Feeder Length For Min. Wire
Size in Steel Conduit
Feet
70
70
70
70
70
70
Feet
380
380
380
380
380
380