Toshiba 4400 Series Installation And Operation Manual page 70

Table of Contents

Advertisement

4400 SPECIFICATIONS: 50kVA w/ Internal Battery Backup
Specification
ENVIRONMENT
Cooling -Forced Air (cfm)
Operating Temperature (°F/°C)
Storage Temperature (°F/°C)
Operating Humidity (%)
Altitude (ft./m)
Location
Heat Rejection at 100% Full Load (BTU/Hour)
Audible Noise (dBA)
MECHANICAL
Weight
lb/(kg)
3
Without Internal Batteries
Dimensions WxDxH (in/mm)
Shipping Weight
lb/(kg)
3
Without Internal Batteries
Shipping Dimensions WxDxH (in/mm)
Clearance (in/mm)
2
Enclosure
Construction
Color
Emergency Power Off (EPO)
Control Panel
MONITORING
Operator Interface (Front Panel)
Dry Contacts Included
RS-232 Interface
Optional – Intelligent Monitoring
Optional – Remote Status Alarm Panel (RSAP)
ADDITIONAL FEATURES
Optional Matching Battery Cabinets
Optional Matching MBS/PDU Cabinet
2 - Minimum front clearance for unobstructed airflow is 20 inches. However, minimum front clearance when
physically accessing the UPS must be at least the width of the front door of the UPS, or per NEC 110.34(A)
(36 i n./900 mm) and local requirements, whichever is greater.
3 - Approximate weights for dual-input units. Actual weights may vary depending on exact UPS configu-
ration.
60
With Internal Batteries
32.1 in x 37.2 in x 73.8 in (816 mm x 944 mm x 1874 mm)
With Internal Batteries
46 in x 48 in x 90 in (1168 mm x 1219 mm x 2286 mm)
4400 Series Installation and Operation Manual – 64527-006
50kVA
5 x 452 cfm (max.
32°F – 104°F (0 °C – 40 °C)
14°F – 122°F (-10 °C – 50 °C)
5 – 95% RH
3300 ft. (1000 m) w/o derating
Indoors in dust and moisture free environment
15,034
<65 dBA
965 lbs. (438 kg)
1920 lbs. (871 kg)
1115 lbs. (506 kg)
2070 lbs. (939 kg)
36 in (900 mm) Front /
16 in (406 mm) Top /
0.0 in (Zero) clearance Sides/Back
NEMA 1
Welded Steel Chassis
Powder Coat, DuPont O'Brien Black
Yes
Touchscreen and LED
Touchscreen and LED
Yes
Yes
Yes – RemotEye 4
Yes
Yes
Yes

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents