D.5 – Cable Size for 3-Phase/3-Wire + G
TABLE D5 – RECOMMENDED OUTPUT/BYPASS CABLE SIZE FOR 3-PHASE/3-WIRE + G
Vin, Vout
3P/3W+G
208V
Phase
220V
Phase
230V
Phase
240V
Phase
380V
Phase
400V
Phase
415V
Phase
480V
Phase
600V
Phase
D.6 – Battery Cabling
15 kVA
#6
Calculated values of Input current at different voltages are listed in Table D.4. Calculated values for Output/
Bypass current at different voltages are listed in Table D.5.
D.7 – Input Transformer Current for Given Input Voltage
TABLE D.7 – INPUT TRANSFORMER CURRENT FOR GIVEN INPUT VOLTAGE
Input
Input Current (Input Currrent + Charging Current) at Full Load (A)
Voltage
15 kVA
208/120V
42 (46)
220/127V
41 (45)
4400 Series Installation and Operation Manual – 64527-006
15kVA
20kVA
25kVA
(AWG)
(AWG)
(AWG)
#6
#6
#6
#6
#10
#8
#8
#8
#10
#8
#12
#10
#12
#10
#10
15kVA
20kVA
25kVA
(AWG)
(AWG)
(AWG)
#6
#4
#8
#6
#8
#6
#8
#6
#10
#10
#10
#10
#10
#10
#12
#10
#12
#12
#10
TABLE D.6 – RECOMMENDED BATTERY CABLING
Recommended Battery Cabinet Cable Size (AWG)
20 kVA
25 kVA
#4
#2
20 kVA
25 kVA
55 (60)
69 (74)
54 (59)
68 (72)
30kVA
50kVA
(AWG)
(AWG)
#4
#3
2/0
#4
#3
2/0
#6
#6
#3
#8
#6
#3
#8
#6
#3
#8
#8
#4
#8
#6
30kVA
50kVA
(AWG)
(AWG)
#3
#2
2/0
#4
#3
1/0
#4
#3
10
#4
#3
1/0
#8
#6
#3
#8
#6
#3
#8
#6
#4
#8
#8
#4
#8
#6
30 kVA
50 kVA
#2
4/0
30 kVA
50 kVA
83 (88)
139 (148)
81 (86)
136 (144)
80kVA
(AWG)
300 kcmil
300 kcmil
2/0
2/0
2/0
1/0
1/0
1
80kVA
(AWG)
300 kcmil
250 kcmil
250 kcmil
250 kcmil
1/0
1/0
1/0
1/0
1/0
80 kVA
500 kcmil
80 kVA
222 (238)
217 (232)
115