Auto Adjust Time - Omron SYSMAC CJ1W-EIP21 Operation Manual

Sysmac cs and cj series ethernet/ip units 100base-tx 100base-tx/10base-t
Hide thumbs Also See for SYSMAC CJ1W-EIP21:
Table of Contents

Advertisement

Using the Automatic Clock Adjustment Function

12-2-3 Auto Adjust Time

The contents in the CPU Bus Unit System Setup that are set for using mail
send and receive functions are shown in the CX-Programmer's Edit Parame-
ters Dialog Box.
Item
Get the time
Enable to set the CPU Unit's clock to the time at the
information from
SNTP server's clock.
the SNTP
The clock can be changed only for the CPU Unit to
server
which the EtherNet/IP Unit or built-in EtherNet/IP port
is mounted.
Auto Adjust
Set the time at which the SNTP server is to be
Time
accessed to synchronize the clocks.
When the time that is set here arrives, the SNTP
server is accessed and the CPU Unit clock is
adjusted to match the SNTP server clock.
Server specifi-
Select whether the SNTP server used for automatic
cation type
clock adjustment is to be specified by IP address or
by host domain name (i.e., by host name).
IP Address
Set the IP address for the SNTP server that is to be
used for automatic clock adjustment.
This setting is enabled only when server specification
by IP address has been selected.
Host name
Set the host domain name (i.e., the host name) for
the SNTP server that is to be used for automatic
clock adjustment.
This setting is enabled only when server specification
by host name has been selected.
Port No.
Set the port number for connecting to the SNTP
server that is to be used for automatic clock adjust-
ment. This setting does not normally need to be
changed.
Contents
Section 12-2
Default
Not
selected
(disabled)
0:0:0
IP Address
0.0.0.0
None
0
(Number
123 is
used.)
327