Using The Automatic Clock Adjustment Function; Specifications; Procedure - Omron SYSMAC CJ1W-EIP21 Operation Manual

Sysmac cs and cj series ethernet/ip units 100base-tx 100base-tx/10base-t
Hide thumbs Also See for SYSMAC CJ1W-EIP21:
Table of Contents

Advertisement

Using the Automatic Clock Adjustment Function

12-1-2 Specifications

12-2 Using the Automatic Clock Adjustment Function

12-2-1 Procedure

1,2,3...
Item
Protocol
SNTP
Port number
123 (UDP)
Can also be set from the CX-Programmer in the Unit Setup.
Adjustment timing
Automatic (fixed time) and manual (manual only cannot be
set)
Access to SNTP
Writes the clock information
server
from the SNTP server to the
local CPU Unit.
Refresh timing
When the automatic clock adjustment switch is turned from
OFF to ON and at a specified time.
1. Make the basic settings.
Refer to Initial Settings on page 34.
2. With the CX-Programmer online, right-click the EtherNet/IP Unit or built-in
EtherNet/IP port in the IO Table Dialog Box of the CX-Programmer, and se-
lect Edit - Unit Setup Set the following on the Auto Adjust Time Tab Page
of the Edit Parameters Dialog Box.
• SNTP server specification (required)
• Access to the SNTP server is enabled when writing clock information from
the SNTP server to the local CPU Unit when the Automatic Clock Adjust-
ment Switch is turned from OFF to ON and at a set automatic adjustment
time.
• Automatic clock adjustment setting.
3. To perform automatic clock adjustment manually, turn the Automatic Clock
Adjustment Switch from OFF to ON. (The Automatic Clock Adjustment
Switch is word n bit 05 in the words allocated in the CPU Bus Unit Area,
where n = CIO 1500 + (25
4. Select Transfer to PLC from the PLC Menu and click the Yes Button. The
Unit Setup (CPU Bus System Setup) will be transferred to the CPU Unit
(the setting data will be transferred to the CPU Bus Unit System Setup Ar-
ea).
Specification
Obtains the clock information
from the SNTP server set up
on the Network, and applies
the information obtained to
the local CPU Unit.
×
unit number.)
Section 12-2
325