Omron SYSMAC CJ1W-EIP21 Operation Manual page 389

Sysmac cs and cj series ethernet/ip units 100base-tx 100base-tx/10base-t
Hide thumbs Also See for SYSMAC CJ1W-EIP21:
Table of Contents

Advertisement

Connection Status Codes and Error Processing
Connection status
General
Additional
Status
Status
(hex)
(hex)
Unique OMRON Error Codes
01
0810
Error code returned from target:
New data could not be obtained
from the CPU Unit when open-
ing connection. (The Unit will
automatically retry, and attempt
to open the connection again.)
01
0811
Error code generated in origina-
tor:
New data could not be obtained
from the CPU Unit when open-
ing connection. (The Unit will
automatically retry, and attempt
to open the connection again.)
Source of error
Configuration 1
This error may
occur if the CPU
Unit's cycle time
was long when
opening the con-
nection, the speci-
fied EM bank was
converted to file
memory, or some
problem in the
PLC caused the
PLC to stop.
If the cycle time
was too long, the
problem will be
resolved automat-
ically. If the EM
bank is set as file
memory, change
the storage loca-
tion for the tag
data. If the PLC
has stopped,
identify and cor-
rect the error.
If the PLC system
is stopped, iden-
tify the cause of
the error from the
CPU Unit error
data.
This error may
occur if the CPU
Unit's cycle time
was long when
opening the con-
nection, or the
specified EM bank
was converted to
file memory.
If the cycle time
was too long, the
problem will be
resolved automat-
ically. If the EM
bank is set as file
memory, change
the storage loca-
tion for the tag
data.
Handling
Configuration 2
Configuration 3
The meaning of this
The meaning of this
error code is defined
error code is defined
by each vendor, so it
by each vendor, so it
depends on the tar-
depends on the origi-
get's specifications.
nator's specifica-
(Contact the target
tions.
device's manufac-
(Contact the origina-
turer.)
tor device's manufac-
turer.)
The meaning of this
The meaning of this
error code is defined
error code is defined
by each vendor, so it
by each vendor, so it
depends on the tar-
depends on the origi-
get's specifications.
nator's specifica-
(Contact the target
tions.
device's manufac-
(Contact the origina-
turer.)
tor device's manufac-
turer.)
Section 14-3
363

Advertisement