Error Log Error Codes - Omron SYSMAC CJ1W-EIP21 Operation Manual

Sysmac cs and cj series ethernet/ip units 100base-tx 100base-tx/10base-t
Hide thumbs Also See for SYSMAC CJ1W-EIP21:
Table of Contents

Advertisement

Error Log Function

14-4-4 Error Log Error Codes

Error
code
(hex)
0001
CPU Unit watchdog timer error
0002
CPU Unit service monitoring error
0006
Other CPU error
000E
I/O bus error
000F
CPU Unit initialization error
0011
Event timed out
0012
CPU Unit memory error
0015
CPU Unit fatal error
0017
Tag database error
0103
Resend count exceeded (send failed)
0105
Node address setting error (send failed)
0107
Remote node not in network (send failed)
0108
No Unit with specified unit address (send
failed)
010B
CPU Unit error (send failed)
010D
Destination address not in routing tables
(send failed)
010E
Not registered in routing tables (send failed)
010F
Routing table error (send failed)
0110
Too many relay points (send failed)
0111
Command too long (send failed)
0112
Header error (send failed)
0117
Internal buffers full; packet discarded
0118
Illegal packet discarded
0119
Local node busy (send failed)
0120
Unexpected routing error
0122
Service not supported in current mode;
packet discarded
0123
Internal send buffer full; packet discarded
0124
Maximum frame size exceeded; routing
failed
0125
Response timeout; packet discarded
020F
Communications controller error
0211
IP address duplication
021A
Logic error in setting table
Error
00 hex
Monitoring time (ms)
Bit D11: Unit not in Registered I/O Tables
(Other bits are reserved for system use.)
00 hex
00 hex
MRC (main command)
01 hex: Read error
02 hex: Write error
00 hex
00 hex
FINS Command:
FINS Response:
CIP Frame:
00 hex
Port number (always 02)
00 hex
Detail code
First byte
00 hex
00 hex
00 hex
SRC (subcommand)
03 hex: Routing tables
50 hex: CPU Bus Unit
Area (CIO or DM)
00 hex
00 hex
Bit 15: OFF
Bits 08 to 14: Source network address
Bits 00 to 07: Source node address
Bit 15: ON
Bits 08 to 14: Destination network address
Bits 00 to 07: Destination node address
FFFF
01 hex
Lower byte of IP address
02 hex: Network parame-
ters
03 hex: Routing tables
04 hex: Unit Setup
0E hex: Unit name
12 hex: Status area layout
setting error
13 hex: Status area layout
setting verification error
15 hex: Installation in a
PLC of another series
(e.g., from CJ1 to CJ2)
after setting the Unit.
Section 14-4
Saved in
EEPROM
Second byte
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
Yes
Yes
Yes
365