Tag Data Link I/O Response Time - Omron SYSMAC CJ1W-EIP21 Operation Manual

Sysmac cs and cj series ethernet/ip units 100base-tx 100base-tx/10base-t
Hide thumbs Also See for SYSMAC CJ1W-EIP21:
Table of Contents

Advertisement

Tag Data Link Performance for CJ2M Built-in EtherNet/IP Ports

10-4-2 Tag Data Link I/O Response Time

292
If the same RPI is set for all connections, 12 ms is the lowest setting that can
be used.
Calculation Example
(1,000 ÷ 12 [ms] (RPI) + 1,000 ÷ 100 [ms] (heartbeat transmission period)) ×
32 (connections) = 2,987 pps < 3,000 pps
Send connections = 16
(20 words × 16 = 320 words)
Node 2
Node 1
Receive 20 words
Send 20 words
Receive 20 words
Send 20 words
Receive 20 words
Receive 20 words
Receive 20 words
Receive 20 words
Receive 20 words
Receive 20 words
With tag data links, if the data in the data link area for a node changes due to
an input to that node, a certain amount of time is required for the data in data
link area at another node to be updated and output.
The I/O response time for tag data links can be calculated for a CJ2M built-in
port in the same was as it can for a CJ2H built-in port (refer to 10-2-4 Chang-
ing the RPI). Here, formulas to calculate guideline I/O response times are pro-
vided. (Tag data link delays are ignored because the data link size handled by
the built-in CJ2M port is small.)
Maximum I/O Response Time
Input ON delay + Cycle time of sending PLC × 2 + RPI + Cycle time of receiv-
ing PLC × 2 + Output ON delay
Minimum I/O Response Time
Input ON delay + Cycle time of sending PLC + Cycle time of receiving PLC +
Output ON delay
Cycle time: 5 ms
Input ON response time:
1.5 ms
Input
Node 3
Receive 20 words
Receive 20 words
Send 20 words
Receive 20 words
Receive 20 words
Receive connections = 16
(20 words × 16 = 320 words)
PLC #1
Node 1
Connection
RPI: 12 ms
20
words
All connections
EtherNet/IP
Data link
Section 10-4
*All nodes use CJ2M built-in ports.
Node 17
Node 16
Receive 20 words
Receive 20 words
Receive 20 words
Receive 20 words
Receive 20 words
Receive 20 words
Send 20 words
Receive 20 words
Send 20 words
Receive 20 words
PLC #2
Node 2
20
Cycle time: 10 ms
words
Output ON response
time: 2.0 ms