Omron SYSMAC CJ1W-EIP21 Operation Manual page 392

Sysmac cs and cj series ethernet/ip units 100base-tx 100base-tx/10base-t
Hide thumbs Also See for SYSMAC CJ1W-EIP21:
Table of Contents

Advertisement

Error Log Function
Error
code
(hex)
0300
Parameter error; packet discarded
0347
I/O refreshing error
03C0
FINS/TCP setting error
03C1
Server settings error
03C2
FINS/TCP packet discarded
03C3
FINS/UDP packet discarded
366
Error
FINS Command:
FINS Response:
CIP Frame:
00 hex
01 to 10 hex:
Connection number
00 hex: DNS
03 hex: SNTP
04 hex: FTP
06 hex: BOOTP
07 hex: SNMP
08 hex: SNMP Trap
09 hex: FINS/UDP
0A hex: FINS/TCP
01 to 10 hex:
Connection number
00 hex
Detail code
First byte
Bit 15: OFF
Bits 08 to 14: Source network address
Bits 00 to 07: Source node address
Bit 15: ON
Bits 08 to 14: Destination network address
Bits 00 to 07: Destination node address
FFFF
00 hex
01: Automatically allo-
cated FINS node address
duplication
02: Destination IP address
error
03: Destination port num-
ber error
01: IP address
02: Host name
03: Port number
04: Other parameter
02 hex: Reopening
because remote node
closed
03 hex: Reopening
because of reception error
04 hex: Reopening
because of transmission
error
05 hex: Reopening
because RST received
from remote node
06 hex: Reopening
because of no keep-alive
response
07 hex: Illegal FINS/TCP
procedure
08 hex: Insufficient mem-
ory during server process-
ing
09 hex: Insufficient mem-
ory during client process-
ing
0A hex: Insufficient mem-
ory during node switching
01 to FE hex:
Source node address
Section 14-4
Saved in
EEPROM
Second byte
No
Yes
No
No
No
No

Advertisement