Using the LED Indicators and Display for Troubleshooting
Indicator
MS
NS
7-segment
Lit red
Not lit
H3
Flashing
Not lit
H4
red
Flashing
Not lit
H6
red
Flashing
Not lit
H7
red
Flashing
---
H8
red
Flashing
---
H9
red
348
Error
Cause
EtherNet/IP
---
Unit or built-in
EtherNet/IP
port faulty
Node address
The node
setting error
address set on
the switches is
invalid (00 or
FF.)
CPU Unit
---
faulty
I/O table not
The CPU Unit's
registered
I/O table is not
registered.
Simple backup
The simple
function
backup func-
restore error
tion's data resto-
ration failed.
I/O bus error
An error
occurred while
exchanging data
with the CPU
Unit.
Unit operation (Flag
Error
status)
log
(hex)
Operation stops.
---
Operation stops.
---
Records the error in
000F
the error log (time/
date all zeroes).
Operation stops.
Operation stops.
0006
The settings of the
---
EtherNet/IP Unit or
built-in EtherNet/IP
port are all cleared,
unless the backup file
does not exist, a
Memory Card is not
mounted, or the PLC
model does not
match.
• If the Unit is the orig-
000E
inator of the tag data
link connection, it
stops communica-
tions.
• If the Unit is the tar-
get of the tag data
link connection and
the PLC status is
included in the com-
munications data,
the corresponding
Target Node PLC
Error Flag will be
turned ON.
Section 14-2
Countermeasure
Replace the Ether-
Net/IP Unit or (for a
built-in EtherNet/IP
port) the CPU Unit
if the error recurs
when the Unit is
restarted.
Set the node
address correctly
and restart the Eth-
erNet/IP Unit or
built-in EtherNet/IP
port.
Replace the CPU
Unit if the error
recurs when the
CPU Unit is
restarted.
Create the I/O
table.
Perform the simple
backup operation
again. If the error
recurs, replace the
Memory Card, or
EtherNet/IP Unit,
or (for a built-in
EtherNet/IP port)
the CPU Unit.
Check and correct
the CPU Unit's
operating environ-
ment.

Advertisement