Communications Cycle Time

8-1-4

Specifying Network Parameters

Note
8-2
Communications Cycle Time
8-2-1

Active Data Links

The network parameters can be specified from the Controller Link Support
Software. This section describes only the allowable setting range for each net-
work parameter. Refer to the Controller Link Support Software Operation
Manual (W308) for setting procedures.
The following table shows the setting range and default for network parame-
ters.
Network parameter
Maximum node address
Number of polled nodes per communications cycle
Maximum no. of event-frames per communications
cycle
The network parameters become valid immediately after being set.
1. The setting range will be 2 to 62 and the default value will be 62 when the
Wired Network 62 Node Enable Bit in the DM Parameter Area software
switches of the CS1W-CLK21-V1 or CJ1W-CLK21-V1 Unit is ON and the
Unit is restarted.
2. Always stop the data link before changing network parameters.
3. Specify a value for the maximum node address that is equal to or greater
than the maximum node address in the Controller Link Network.
4. For the CVM1 and CV-series PLCs, always set the System Protect Key
Switch on the CPU Unit to NORMAL. Otherwise, the network parameter
settings will not be stored normally.
5. The maximum node address cannot be changed to 32 when the Wired
Network 62 Node Enable Bit is ON in the DM Parameter Area software
switches of a CS1W-CLK21-V1 or CJ1W-CLK21-V1 Unit with unit version
1.2 or later.
This section describes how to calculate the communications cycle time.
The following equations are used to calculate the communications cycle time
when data links are operating.
Wired Systems
Baud rate
2 Mbps
10
A + 600
1 Mbps
18
A + 1,150
500 Kbps
34
A + 2,260
Note A: Total number of data link words within the network
(total number of words in send areas of all nodes)
B: Number of polled nodes per comm cycle
(value specified in the network parameters)
C: Number of nodes connected to the network
D: Number of nodes that send messages during the
communications cycle
Equation
B + 290
C + 320
D + 4
B + 370
C + 360
D + 8
B + 530
C + 440
D + 16
Section 8-2
Setting
Default
range
value
2 to 32
32
(See note 1.)
(See note
1.)
1 to 31
4
6 to 238
35
E + 3,290 ( s)
E + 3,770 ( s)
E + 4,730 ( s)
251