Coordinator Module - Omron HOME SECURITY SYSTEM - MOTION SENSOR FQM1-CM001 Operation Manual

Fqm1 series flexible motion controller
Table of Contents

Advertisement

Coordinator Module

Note
2-3
Coordinator Module
Nomenclature
FLEXIBLE
RDY
MOTION
RUN
CONTROLLER
ERR
PRPHL
COMM1
COMM2
PERIPHERAL
Peripheral
port
PORT
RS-232C
port
Coordinator Module
Note
Indicators
34
(1) The inrush current is given for a cold start at room temperature with an
AC power supply. The AC inrush control circuit uses a thermistor element
with a low-temperature current control characteristic. If the ambient tem-
perature is high or the FQM1 is hot-started, the thermistor will not be suf-
ficiently cool, and the inrush currents given in the table may be exceeded
by up to twice the given values. When selecting fuses or breakers for ex-
ternal circuits, allow sufficient margin in shut-off performance. If the
FQM1 is hot-started, the capacitor will not be discharged, and the inrush
currents given in the table may be exceeded by up to twice the given val-
ues.
(2) Disconnect the Power Supply Unit's LG terminal from the GR terminal
when testing insulation and dielectric strength. Testing the insulation and
dielectric strength with the LG terminal and the GR terminals connected
will damage internal circuits.
CM001
Peripheral
port baud rate
ON
OFF
detection/System
Setup switch
1
2
40-pin connector
CN1
24 general-purpose
I/O points and RS-422A
RS422
39
40
Cover the peripheral port and RS-232C port with the supplied covers when
the ports are not being used to prevent dust contamination.
Indicator Color
RDY
Green Module operation
RUN
Green Program execution Lit
ERR
Red
Module error
Indicators
FLEXIBLE
MOTION
CONTROLLER
Name
Status
Lit
The Module is operating normally.
Not lit
Module error (e.g., WDT error).
Executing internal Module program.
Not lit
Internal Module program stopped.
Lit
Fatal error.
Flash-
Non-fatal error.
ing
Not lit
Module operating normally.
Section 2-3
CM001
RDY
RUN
ERR
PRPHL
ON
OFF
COMM1
COMM2
Meaning