Number Name Settings Default Or Both Eim; To 12 Cph; Both No; Not Displayed If - Honeywell TH8320R1003 Vision Pro 8000 Product Data

Hide thumbs Also See for TH8320R1003 Vision Pro 8000:
Table of Contents

Advertisement

ISU
Installer Setup
Number
Name
314
Cool Cycles Per
1 to 6 CPH
Hour Stage 3
314
Cool Cycles Per
1 to 6 CPH
Hour Stage 4
315
Heat Cycles Per

1 to 12 CPH

Hour Stage 1
Note: Depending
on the application,
the text displayed
on the screen may
show the specific
heating equipment
type. "Stage 1" is

not displayed if

there is only 1

stage.
Table 2. Installer Setup (ISU) Table. (Continued)
Settings
Default
3
3
Conv. Forced
Air = 5 CPH
Heat Pump = 3
CPH
Radiant Heat =
3 CPH
31
VISIONPRO
Residential,
Commercial
Requires
or Both
EIM
Commercial
No
This ISU is only displayed when ISU 101
Application is set to Commercial and ISU 207
Cool Stages is set to 3 stages.
Cycle rate limits the maximum number of
times the system can cycle in a 1 hour period
measured at a 50% load. For example, when
set to 3 CPH, at a 50% load, the most the
system will cycle is 3 times per hour (10
minutes on, 10 minutes off). The system
cycles less often when load conditions are
less than or greater than a 50% load.
Commercial
Yes
This ISU is only displayed when ISU 101
Application is set to Commercial and ISU 207
Cool Stages is set to 4 stages.
Cycle rate limits the maximum number of
times the system can cycle in a 1 hour period
measured at a 50% load. For example, when
set to 3 CPH, at a 50% load, the most the
system will cycle is 3 times per hour (10
minutes on, 10 minutes off). The system
cycles less often when load conditions are
less than or greater than a 50% load.
Both
No
This ISU is only displayed when ISU 207 Heat
Stages is set to 1 stage.
Cycle rate limits the maximum number of
times the system can cycle in a 1 hour period
measured at a 50% load. For example, when
set to 3 CPH, at a 50% load, the most the
system will cycle is 3 times per hour (10
minutes on, 10 minutes off). The system
cycles less often when load conditions are
less than or greater than a 50% load. The
recommended cycle rate settings are below
for each heating equipment type:
Standard Efficiency Gas Forced Air = 5 CPH
High Efficiency Gas Forced Air = 3 CPH
Oil Forced Air = 5 CPH
Electric Forced Air = 9 CPH
Hot Water Fan Coil = 3 CPH
Hot Water Radiant Heat = 3 CPH
Geothermal Radiant Heat = 3 CPH
Steam = 1 CPH
Gravity = 1 CPH
®