Honeywell TH8320R1003 Vision Pro 8000 Product Data page 28

Hide thumbs Also See for TH8320R1003 Vision Pro 8000:
Table of Contents

Advertisement

®
VISIONPRO
8000 WITH REDLINK™
ISU
Installer Setup
Number
Name
306
Compressor Heat
Comfort
Diff. Stage 1
1.0° F to 4.0° F from setpoint (in
0.5° F increments)
306
Compressor Heat
Comfort
Diff. Stage 2
1.0° F to 4.5° F from setpoint (in
0.5° F increments)
308,
Backup Heat
Comfort
309
Droop Stage 1
2.0° F to 15.0° F from setpoint (in
0.5° F increments)
Note: "Stage 1" is
not displayed if
there is only 1
stage of Backup
Heat.
68-0312—01
Table 2. Installer Setup (ISU) Table. (Continued)
Settings
Default
Comfort
Comfort
Comfort
28
Residential,
Commercial
Requires
or Both
EIM
Both
No
ISU 301 Control Options must be set to
Advanced to view or adjust this ISU.
This ISU is only displayed if ISU 201 Heating
Equipment is Geothermal Radiant and ISU
205 Geo Forced Air is set to Heating and
Cooling.
The indoor temperature must drop to the
selected differential setting before the
thermostat will turn on the stage of heating.
For example, if stage 1 is set to 2° F (1.0° C),
the indoor temperature must be 2° F (1.0° C)
away from the setpoint before stage 1 turns
on. When set to Comfort, the thermostat will
use the stage of heating as needed to keep the
indoor temperature within 1° F (0.5° C)
degree of the setpoint.
Both
No
ISU 301 Control Options must be set to
Advanced to view or adjust this ISU.
This ISU is only displayed if ISU 201 Heating
Equipment is Air to Air Heat Pump,
Geothermal or Geothermal Radiant and there
are 2 compressor stages.
The indoor temperature must drop to the
selected differential setting before the
thermostat will turn on the stage of heating.
For example, if stage 2 is set to 2° F (1.0° C),
the indoor temperature must be 2° F (1.0° C)
away from the setpoint before stage 2 turns
on. When set to Comfort, the thermostat will
use the stage of heating as needed to keep the
indoor temperature within 1° F (0.5° C)
degree of the setpoint.
Both
No
A backup heat droop can be set on any system
that has more than one heating equipment
type.
See "Backup Heat Droop" beginning on
page 75.
The Comfort setting is NOT available for Dual
Fuel systems. For example, Heat Pumps with
Gas Forced Air.
Notes