VISIONPRO
8000 WITH REDLINK™
ISU
Installer Setup
Number
Name
1002
Ventilation Wiring
None
U1
U2
U3
1005
Ventilation
ASHRAE
Method
Percent On Time
1006
Vent Fan Control
Tstat Controls Fan
Equip Controls Fan
1009
Number of
1 to 6
Bedrooms
1009
Size of House
1000 to 5000 sq. ft. (in 100 sq. ft.
increments)
(90 to 460 sq. m.)
1010
Ventilation Rate
30 to 350 CFM (in 5 CFM
increments)
(850 - 9900 LPM)
1012
Vent Percent On
10% to 100% (in 10%
increments)
Time
68-0312—01
Table 2. Installer Setup (ISU) Table. (Continued)
Settings
Default
Thermostat
defaults to the
next unused
universal
terminal (U1,
U2, U3).
Defaults to
ASHRAE
when ISU 101
Application is
set to
Residential.
Percent on
Time is the
only choice
when ISU 101
Application is
set to
Commercial.
Tstat Controls
Fan
2 bedrooms
1000 sq. feet
150
30%
52
Residential,
Commercial
Requires
or Both
EIM
Both
No
Number of Universal Outputs:
TH8321 Thermostat: U1 terminals
Equipment Interface Module (EIM): U1, U2
and U3 terminals
U1, U2, U3 are dry contacts that require
power. See "Wiring IAQ Equipment or a Heat/
Cool Stage to the Universal Terminals"
beginning on page 128.
Both
No
See "Ventilation Control Methods (ISU 1005)"
beginning on page 90.
Both
No
Tstat Controls Fan: The thermostat turns on
the ventilation equipment and the fan when
ventilation is needed.
Equip Controls Fan: The thermostat turns on
the ventilation equipment when ventilation is
needed. The fan is controlled by the
equipment.
Residential
No
This ISU is only displayed when ISU 1005
Ventilation Method is set to ASHRAE
(Residential only).
Residential
No
This ISU is only displayed when ISU 1005
Ventilation Method is set to ASHRAE
(Residential only).
Residential
No
This ISU is only displayed when ISU 1005
Ventilation Method is set to ASHRAE
(Residential only).
Both
No
The thermostat operates ventilation
equipment based on a percentage entered in
the installer setup (ISU 1012). For example, if
Percent on Time is set to 50%, the ventilation
equipment will run at random times during a 1
hour period until it reaches a 50% run time
(approximately 30 minutes).
Notes