Honeywell TH8320R1003 Vision Pro 8000 Product Data page 27

Hide thumbs Also See for TH8320R1003 Vision Pro 8000:
Table of Contents

Advertisement

ISU
Installer Setup
Number
Name
304
Radiant Heat Diff.
Comfort
Stage 2
1.0° F to 3.5° F from setpoint (in
0.5° F increments)
305
Heat Differential
Comfort
Stage 2
1.0° F to 3.5° F from setpoint (in
0.5° F increments)
Note: Depending
on the application,
the text displayed
on the screen may
show the specific
heating equipment
type
305
Heat Differential
Comfort
Stage 3
1.0° F to 4.0° F from setpoint (in
0.5° F increments)
Note: Depending
on the application,
the text displayed
on the screen may
show the specific
heating equipment
type
Table 2. Installer Setup (ISU) Table. (Continued)
Settings
Default
Comfort
Comfort
Comfort
27
VISIONPRO
Residential,
Commercial
Requires
or Both
EIM
Both
No
ISU 301 Control Options must be set to
Advanced to view or adjust this ISU.
This ISU is only displayed if ISU 201 Heating
Equipment is Geothermal Radiant and there
are 2 radiant heat stages.
The indoor temperature must drop to the
selected differential setting before the
thermostat will turn on the stage of heating.
For example, if stage 2 is set to 2° F (1.0° C),
the indoor temperature must be 2° F (1.0° C)
away from the setpoint before stage 2 turns
on. When set to Comfort, the thermostat will
use the stage of heating as needed to keep the
indoor temperature within 1° F (0.5° C)
degree of the setpoint.
Both
No
ISU 301 Control Options must be set to
Advanced to view or adjust this ISU.
This ISU is only displayed for conventional
systems that have 2 heat stages.
The indoor temperature must drop to the
selected differential setting before the
thermostat will turn on the stage of heating.
For example, if stage 2 is set to 2° F (1.0° C),
the indoor temperature must be 2° F (1.0° C)
away from the setpoint before stage 2 turns
on. When set to Comfort, the thermostat will
use the stage of heating as needed to keep the
indoor temperature within 1° F (0.5° C)
degree of the setpoint.
Both
No
ISU 301Temperature Control Options must be
set to Advanced to view or adjust this ISU.
This ISU is only displayed for conventional
systems that have 3 heat stages.
The indoor temperature must drop to the
selected differential setting before the
thermostat will turn on the stage of heating.
For example, if stage 3 is set to 2° F (1.0° C),
the indoor temperature must be 2° F (1.0° C)
away from the setpoint before stage 3 turns
on. When set to Comfort, the thermostat will
use the stage of heating as needed to keep the
indoor temperature within 1° F (0.5° C)
degree of the setpoint.
®
8000 WITH REDLINK™
Notes