VISIONPRO
8000 WITH REDLINK™
ISU
Installer Setup
Number
Name
303
Cool Differential
Comfort
Stage 2
1.0° F to 3.5° F from setpoint (in
0.5° F increments)
303
Cool Differential
Comfort
Stage 3
1.0°F - 4.0°F from setpoint (in
0.5° F increments)
303
Cool Differential
Comfort
Stage 4
1.0° F to 4.5° F from setpoint (in
0.5° F increments)
68-0312—01
Table 2. Installer Setup (ISU) Table. (Continued)
Settings
Default
Comfort
Comfort
Comfort
26
Residential,
Commercial
Requires
or Both
EIM
Both
No
ISU 301 Control Options must be set to
Advanced to view or adjust this ISU.
This ISU is only displayed when the
thermostat is set to 2 cool stages.
The indoor temperature must rise to the
selected differential setting before the
thermostat turns on the stage of cooling. For
example, if stage 2 is set to 2° F (1.0° C), the
indoor temperature must be 2° F (1.0° C)
away from the setpoint before stage 2 turns
on. When set to Comfort, the thermostat uses
the stage of cooling as needed to keep the
indoor temperature within 1° F (0.5° C)
degree of the setpoint.
Commercial
No
ISU 301 Control Options must be set to
Advanced to view or adjust this ISU.
This ISU is only displayed when the
thermostat is set to 3 cool stages.
The indoor temperature must rise to the
selected differential setting before the
thermostat turns on the stage of cooling. For
example, if stage 3 is set to 2° F (1.0° C), the
indoor temperature must be 2° F (1.0° C)
away from the setpoint before stage 3 turns
on. When set to Comfort, the thermostat uses
the stage of cooling as needed to keep the
indoor temperature within 1° F (0.5° C)
degree of the setpoint.
Commercial
Yes
ISU 301 Control Options must be set to
Advanced to view or adjust this ISU.
This ISU is only displayed when the
thermostat is set to 4 cool stages.
The indoor temperature must rise to the
selected differential setting before the
thermostat turns on the stage of cooling. For
example, if stage 4 is set to 2° F (1.0° C), the
indoor temperature must be 2° F (1.0° C)
away from the setpoint before stage 4 turns
on. When set to Comfort, the thermostat uses
the stage of cooling as needed to keep the
indoor temperature within 1° F (0.5° C)
degree of the setpoint.
Notes