Honeywell TH8320R1003 Vision Pro 8000 Product Data page 120

Hide thumbs Also See for TH8320R1003 Vision Pro 8000:
Table of Contents

Advertisement

®
VISIONPRO
8000 WITH REDLINK™
Typical wiring of a heat pump system with up to four-stage heat and two-stage cool with one transformer.
2
1 See guides on following pages for geothermal radiant heat wiring.
2 Wire a maximum of 4 sensors using the S1-S4 terminals. S1-S4 terminals can be connected to an indoor sensor, outdoor sen-
sor, discharge sensor, return sensor, dry contact device to display an alert or an occupancy sensor for remote setback..
3 L/A terminal sends continuous output when thermostat is set to EM HEAT mode, except when set up for Economizer or TOD.
See "Economizer Module Wiring Diagrams" beginning on page 131.
4 Connect wireless adapter to ABCD for extended wireless range.
68-0312—01
EIM
POWER
HEAT
COOL
STATUS
FAN
LEDS
U1
U2
U3
A
B
4
C
D
S4
CONNECT OPTIONAL
S4
SENSORS TO
S3
S3 AND S4 TERMINALS
S3
Fig. 314. EIM wiring guide — heat pump systems.
TO THERMOSTAT
O/B
HEAT PUMP
O/B
AUX1
AUX1
AUX2
AUX2
Y
L/A
Y2
3
G
L/A
3
1
R
C
CONNECT OPTIONAL
SENSORS
S1 AND S2 TERMINALS
2
120
CHANGEOVER VALVE
BACKUP HEAT
STAGE 1
BACKUP HEAT
STAGE 2
COMPRESSOR
STAGE 1
COMPRESSOR
STAGE 2
FAN RELAY
COMPRESSOR
MONITOR OR
ZONE PANEL
JUMPERS
AIR HANDLER
TRANSFORMER
24
120
VAC
VAC
SENSORS TO

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Th8321r1001 vision pro 8000Th8110r1008 vision pro 8000

Table of Contents