Economizer And Time Of Day (Tod) Operation - Honeywell TH8320R1003 Vision Pro 8000 Product Data

Hide thumbs Also See for TH8320R1003 Vision Pro 8000:
Table of Contents

Advertisement

3. Select Normally Open when Occupied or Normally
Closed when Occupied based on the type of dry contact
device installed.
NOTE: Normally Open when Occupied: The Dry
Contact device is open when the room is occu-
pied and will close when the room is unoccu-
pied.
Normally Closed when Occupied: The Dry
Contact device is closed when the room is
occupied and will open when the room is unoc-
cupied.
Fig. 292.
4. Select a Remote Setback Time Delay. The Remote Set-
back Time Delay forces the thermostat to wait before it
switches from occupied settings to the Remote Setback
settings. When set to 0 minutes, the thermostat will
switch from occupied settings to the Remote Setback
settings immediately when the room is unoccupied.
Fig. 293.
5. Select the Remote Setback settings that you would like
to maintain when the occupancy sensor detects the
room is unoccupied.
Economizer and Time of Day (TOD)
Operation
Economizer
The thermostat controls an economizer module to provide
ventilation during occupied periods and free cooling when
outdoor conditions are favorable. In some climates the cooling
system may run several hours when it may not be required to
maintain indoor comfort. When outdoor conditions are
favorable, ventilation with outdoor air can achieve the same
level of comfort at lower cost. Table 5 explains how the
Economizer Module is controlled by the thermostat.
The thermostat works with the W7220, W7212, W7213 and
W7214 Economizer Modules for both heat pump and
conventional systems.
Table 5. Economizer Operation.
Thermostat Mode
Occupied
Occupied
temporarily
Occupied
Occupied
temporarily
Pre-occupancy
purge
Unoccupied
Unoccupied
temporarily
Standby
Unoccupied
Unoccupied
temporarily
Standby
Non-programmable Fan running
Non-programmable Fan NOT running
105
®
VISIONPRO
8000 WITH REDLINK™
Fig. 294.
A-L/A terminal:
Equipment Operation
Heat/Cool/Fan running
Heat/Cool/Fan running
Heat/Cool/Fan NOT
running
Heat/Cool/Fan NOT
running
ON
Fan running
Cooling system running
Cooling system running
Cooling system running
Cooling system NOT
running
OFF
Cooling system NOT
running
Cooling system NOT
running
ON
OFF
Economizer
68-0312—01