Function Group 2 (N050 Through N079) - Omron SYSDRIVE 3G3MV Setup Manual

Sysdrive 3g3mv series multi-function compact inverter
Hide thumbs Also See for SYSDRIVE 3G3MV:
Table of Contents

Advertisement

List of Parameters
H Function Group 2 (n050 through n079)
Param-
Reg-
Name
eter
ister
No.
No.
(Hex)
n050
0132
Multi-
function
input 1
input 1
(Input ter-
minal S1)
n051
0133
Multi-
function
input 2
(Input ter-
minal S2)
n052
0134
Multi-
function
input 3
(Input ter-
minal S3)
n053
0135
Multi-
function
input 4
(Input ter-
minal S4)
n054
0136
Multi-
function
input 5
(Input ter-
minal S5)
n055
0137
Multi-
function
input 6
( p
(Input ter-
minal S6)
i
l S6)
Note Inverter overheating warning (setting value: 26) can be set for 5.5-kW and 7.5-kW Inverters only.
3-12
Description
Used to select the functions of multi-func-
tion input terminals S1 through S7.
Set
Function
value
0
Forward/
3-wire sequence
Reverse
(to be set in n052
rotation
only)
command
By setting to 0,
the set values in
n050 and n051
are ignored and
the following set-
tings are forcibly
made.
made.
S1: RUN input
(RUN when ON)
S2: STOP input
(STOP when
OFF)
S3: Forward/Re-
verse rotation
command (OFF:
Forward; ON:
Reverse)
1
Forward/
Forward rotation
Stop
command in
2-wire sequence.
(Forward rotation
with the signal
turned ON)
2
Reverse/
Reverse rotation
Stop
command in
2-wire sequence
(Reversed with
the terminal
turned ON)
3
External
ON: External fault
fault (NO)
(EFj detection:
j is a terminal
number)
4
External
OFF: External
fault (NC)
fault (EFj detec-
tion: j is a termi-
nal number)
Setting
range
1 to 33
(26 See
note.)
note )
Description
1 to 33
(26 See
note.)
0 to 33
(26 See
note.)
1 to 33
(26 See
note.)
1 to 33
(26 See
note.)
1 to 33
(26 See
note.)
Chapter 3
Default
Chan-
Memo
setting
ges
during
opera-
tion
1
No
2
No
3
No
5
No
6
No
7
No