List of Parameters
Param-
Reg-
Name
eter
ister
No.
No.
(Hex)
n116 0174
Stall pre-
vention
accelera-
tion/de-
celeration
time set-
ting
n117 0175
Undertor-
que
detection
function
selection
n118 0176
Undertor-
que
detection
level
n119 0177
Undertor-
que
detection
time
3-30
Description
Sets the acceleration/deceleration time for
the stall prevention function during opera-
tion.
0: Accelerates or decelerates according to
acceleration/deceleration time 1 or 2,
whichever is selected.
1: Accelerates or decelerates according to
acceleration/deceleration time 2.
(n021/n022).
Note When a faster (or slower) accelera-
tion/deceleration time is desired, set
this parameter to "1" and set the de-
sired acceleration/deceleration time
for stall prevention operation in ac-
celeration/deceleration time 2.
Sets the undertorque detection function.
0: Undertorque detection disabled.
1: Undertorque detection only when speed
coincides and operation continues
(issues alarm).
2: Undertorque detection only when speed
coincides and output turned OFF (for
protection).
3: Undertorque always detected and
operation continues (issues alarm).
4: Undertorque always detected and output
turned OFF (for protection)
Sets the detection level for undertorque
detection.
Sets the detection time for undertorque
detection.
Chapter 3
Set-
Default
Chan-
ting
setting
ges
range
during
opera-
tion
0, 1
0
No
0 to 4
0
No
0 to
10%
No
200
0.1 to
0.1 s
No
10.0
(s)