List of Parameters
Param-
Regis-
Name
eter
ter No.
No.
(Hex)
n035
0123
Frequency
reference
setting/dis-
play unit
selection
n036
0124
Rated motor
current
Description
Set the unit of frequency refer-
ence and frequency-related val-
ues to be set or monitored
through the Digital Operator.
0: 0.01 Hz
1: 0.1%
2 to 39: rpm (number of motor
poles)
40 to 3,999: The value to be set
or monitored at max. frequency.
Set the value as shown below.
jjjj
Three digits
Decimal place
(See note below)
Note To display 50.0, for exam-
ple, set the value to 1500.
The setting unit of each
parameter or monitor item
below varies with the deci-
mal place.
• Parameters: n024 through n032
and n120 through n127
• Monitor Items: U-01 and U-02
Used to set the rated motor current
for motor overload detection (OL1)
based on the rated motor current.
Note In vector control mode, this
parameter is used as a con-
stant for vector control
operation.
Note Motor overload detection
(OL1) is disabled by setting
the parameter to 0.0.
Note The rated motor current is
default to the standard rated
current of the maximum
applicable motor.
Chapter 3
Setting
Default
Chan-
range
setting
ges
during
opera-
tion
0 to
0
No
3,999
0.0 to
Varies
No
150%
with the
of rated
capac-
output
ity
current
of the
Inverter
Memo
3-9