Omron SYSDRIVE 3G3MV Setup Manual page 74

Sysdrive 3g3mv series multi-function compact inverter
Hide thumbs Also See for SYSDRIVE 3G3MV:
Table of Contents

Advertisement

List of Parameters
Param-
Reg-
Name
eter
ister
No.
No.
(Hex)
n060
013C
Fre-
quency
reference
gain
n061
013D
Fre-
quency
reference
bias
n062
013E
Analog
frequency
reference
filter time
constant
n063
---
Not used
n064
0140
Frequen-
cy refer-
ence loss
detection
(See
note.)
n065
0141
Multi-
function
analog
output
type
selection
Note Frequency reference loss (setting value: 20) can be set for 5.5-kW and 7.5-kW Inverters only.
3-20
Description
Used to set the input characteristics of
analog frequency references.
Gain: The frequency of maximum analog
input (10 V or 20 mA) in percentage based
on the maximum frequency as 100%.
on the maximum frequency as 100%
Bias: The frequency of minimum analog
input (0 V or 0 or 4 mA) in percentage
based on the maximum frequency as
100%.
Used to set the digital filter with a first-or-
der lag for analog frequency references to
be input.
---
Selects the frequency loss detection func-
tion for when the frequency reference from
the control circuit terminal suddenly drops.
0: Disable (Operate according to frequency
reference.)
1: Enable (Continue operation at 80% of
frequency reference prior to loss.)
Note: Frequency reference loss: Frequen-
cy reference voltage drop of 90% within
400 ms.
Selects the multi-function analog output
type.
0: Analog voltage output (functions set in
n066)
1: Pulse train output (functions set in n150)
Chapter 3
Set-
Default
Chan-
ting
setting
ges
range
during
opera-
tion
0 to
100
Yes
255
–100
0
Yes
to 100
0.00
0.10
Yes
to
2.00
---
---
---
0, 1
0
No
0, 1
0
No
Memo