Parameter
Analog input display unit changing (Pr. 241)
The level display for the analog signal connected to terminal 2 or terminal 4 can be switched
between a % display and a display in V or mA.
Depending on the terminal input specification set to Pr. 73, Pr. 267 and voltage/current input
switch, the display units of C3 (Pr. 902), C4 (Pr. 903), C6 (Pr. 904) C7 (Pr. 905) change as shown
below.
Analog Command (terminal 2, 4)
(according to Pr. 73, Pr. 267,
voltage/current input switch)
Tab. 6-110: Units when displaying the set value
Note that the LEDs V or A also light up as an additional indicator when Pr. 241 is set to "1" and
the display is set to the settings for C3/C4, C6/C7 or C13/C15.
NOTES
Analog input display is not displayed correctly if voltage is applied to terminal 1 when termi-
nal 1 input specifications (0 to ±5V, 0 to ±10V) and main speed (terminal 2, terminal 4 input)
specifications (0 to 5V, 0 to 10V, 0 to 20mA) differ. (For example, 5V (100%) is analog dis-
played when 0V and 10V are applied to terminal 2 and terminal 1 respectively in the initial
status.
Set "0" (initial value is 0% display) in Pr. 241 to use.
FR-A700 EC
Frequency/torque setting by analog input (terminals 1, 2 and 4)
0 to 5V input
0 to 10V input
0/4 to 20mA input
Pr. 241 = 0 (initial value)
0 to 5V → 0 to 100% (0.1%) is
displayed.
0 to 10V → 0 to 100% (0.1%) is
displayed.
0 to 20mA → 0 to 100% (0.1%) is
displayed.
Pr. 241 = 1
0 to 100% → 0 to 5V (0.01V) is
displayed.
0 to 100% → 0 to 10V (0.01V) is
displayed.
0 to 100% → 0 to 20mA (0.01mA) is
displayed.
6 - 387