Mitsubishi Electric FR-A700 Instruction Manual page 414

Frequency inverter
Hide thumbs Also See for FR-A700:
Table of Contents

Advertisement

Selection and protection of a motor
Pr.
82
90
91
92
93
94
859
Tab. 6-59: Setting of parameter 82, 90 to 94 and 859
Refer to the following table and set Pr. 83 and Pr. 84.
Pr.
83
84
Tab. 6-60: Setting of parameter 83 and 84
NOTE
When "9999" is set in Pr. 90 to Pr. 94, Mitsubishi motor (SF-JR, SF-HR, SF-JRCA, SF-HRCA)
constants are used.
6 - 234
Name
01800 or less
Motor excitation cur-
rent (no load current)
02160 or more
01800 or less
Motor constant R1
02160 or more
01800 or less
Motor constant R2
02160 or more
01800 or less
Motor constant L1
02160 or more
01800 or less
Motor constant L2
02160 or more
01800 or less
Motor constant X
02160 or more
01800 or less
Torque current
02160 or more
Name
Motor rated voltage
Rated Motor Frequency
Setting Range
0–500A, 9999
0–3600A, 9999
0–50Ω, 9999
0–400mΩ, 9999
0–50Ω, 9999
0–400mΩ, 9999
0–50Ω, 9999
0–3600mΩ, 9999
0–50Ω, 9999
0–3600mΩ, 9999
0–500Ω, 9999
0–100Ω, 9999
0–500A, 9999
0–3600A, 9999
Setting Range
Setting Inrements
0–1000V
10–120Hz
Parameter
Setting Inre-
Initial Value
ments
0.01A
9999
0.1A
0.001Ω
9999
0.01mΩ
0.001Ω
9999
0.01mΩ
0.001Ω
9999
0.01mΩ
0.001Ω
9999
0.01mΩ
0.01Ω
9999
0.01A
9999
0.1A
Initial Value
0.1V
400V
0.01Hz
50Hz

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-a740 ecFr-a700 ec

Table of Contents