Mitsubishi Electric FR-A700 Instruction Manual page 185

Frequency inverter
Hide thumbs Also See for FR-A700:
Table of Contents

Advertisement

Parameter
Parameter
Func-
Name
tion
14
Load pattern selection
15
Jog frequency
Jog acceleration/
16
deceleration time
17
MRS input selection
18
Refer to Pr. 1 and Pr. 2
19
Refer to Pr. 3
20
Refer to Pr. 7 and Pr. 8
21
Tab. 6-1:
Parameter overview (5)
FR-A700 EC
Incre-
Initial
Setting
ments
Value
Range
0
1
2
3
1
0
4
5
0.01 Hz
5Hz
0–400Hz
0.1/
0–3600s/
0.5s
0.01 s
360s
0
2
1
0
4
Description
For constant torque load
For variable-torque load
Boost for reverse
rotation 0%
For constant
torque lift
Boost for forward
rotation 0%
RT signal ON: For constant-torque
load (same as in setting 0)
RT signal OFF: For constant-torque
lift, boost for reverse rotation 0%
(same as in setting 2)
RT signal ON: For constant-torque
load (same as in setting 0)
RT signal OFF: For constant-torque
lift, boost for forward rotation 0%
(same as in setting 3)
Set the frequency for jog
operation.
Set the acceleration/deceleration
time for jog operation. Set the time
taken to reach the frequency set in
Pr. 20 "Acceleration/deceleration
reference frequency" for accelera-
tion/deceleration time (initial value
is 50Hz).
In addition, acceleration/decelera-
tion time can not be set separately.
Open input always
Normally closed input (NC contact
input specifications)
External terminal: Normally closed
input (NC contact input specifica-
tions)
Communication: Normally open
input
Parameter overview
All
Para-
Para-
para-
meter
meter
meter
copy
clear
Refer
clear
to
page
✔: enabled
—: disabled
6-175
6-186
6-290
6 - 5

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-a740 ecFr-a700 ec

Table of Contents