Motor brake and stop operation
BOF signal: Brake opening request signal
BRI signal: Brake opening completion signal
Fig. 6-110: Connection example with mechanical brake (Pr. 184 = 15, Pr. 190 = 20)
The input signal terminal used differs according to the Pr. 178 to Pr. 189 settings.
The output signal terminal used differs according to the Pr. 190 to Pr. 196 settings.
The current should be within the permissible current of the transistor in the inverter.
(24V/ 0.1A DC)
NOTES
When brake sequence mode is selected, automatic restart after instantaneous power failure
is invalid.
When using this function, set the acceleration time to 1s or longer.
Changing the terminal function using any of Pr. 178 to Pr. 186 and Pr. 190 to Pr. 196 may
affect the other functions. Make setting after confirming the function of each terminal.
6 - 262
Power
supply
Start signal
Multi-speed signal
BRI signal
MC
Mechanical
brake
Motor
24V DC
MC
Parameter
BOF signal
I001570E