Acceleration and deceleration
6.11.4
Shortest acceleration/deceleration (automatic acceleration/deceleration)
(Pr. 61 to Pr. 63, Pr. 292, Pr. 293)
The inverter operates in the same conditions as when appropriate values are set in each para-
meter even if acceleration/deceleration time and V/f pattern are not set. This function is useful
when you just want to operate, etc. without fine parameter setting.
Pr.
Initial
Name
No.
Value
Reference cur-
61
9999
rent
Reference value
62
9999
at acceleration
Reference value
63
9999
at deceleration
Automatic accel-
292
eration/decelera-
tion
Acceleration/
293
deceleration sep-
arate selection
When Pr. 570 Multiple rating setting ≠ "2", performing all parameter clear and inverter reset
changes the setting range (refer to section 6.7.5).
6 - 208
Setting Range
Description
01800
0–500A
or less
Set the reference current during shortest /
02160
optimum acceleration/deceleration.
or
0–3600A
more
Rated inverter output current value is refer-
9999
ence
Set the limit value during shortest / optimum
0–220%
acceleration.
Shortest acceleration: 150% is a limit value
9999
Optimum acceleration: Pr. 61 is reference
Set the limit value during shortest / optimum
0–220%
deceleration.
Shortest deceleration: 150% is a limit value
9999
Optimum deceleration: Pr. 61 is reference
0
Normal mode
Shortest acceleration/deceleration (without
1
brake)
Shortest acceleration/deceleration (with
11
brake)
0
3
Optimum acceleration/deceleration
5/6
Elevator mode 1, 2 (Refer to section 6.9.3)
Brake sequence mode 1, 2
7/8
(Refer to section 6.13.5.)
Both acceleration and deceleration are made
0
in the shortest acceleration/deceleration
mode
0
Only acceleration is made in the shortest
1
acceleration/deceleration mode
Only deceleration is made in the shortest
2
acceleration/deceleration mode
Parameter
Refer to
Parameters referred to
Section
0
Torque boost
6.7.1
7
Acceleration
6.11.1
time
8
Deceleration
6.11.1
time
22
Stall prevention
6.7.4
operation level
22
Torque limiter
6.3.2