Function assignment of external terminals
6.14.3
Condition selection of function validity by the second function selection
signal (RT) and third function selection signal (X9) (RT signal, X9 signal,
Pr. 155)
You can select the second (third) function using the RT(X9) signal.
You can also set the condition (reflection conditon) where the second function and third function
become valid.
Pr.
Name
No.
RT signal function validity
155
condition selection
When the RT signal turns on, the second function becomes valid.
When the X9 signal turns on, the third function becomes valid.
For the X9 signal, set "9" in any of Pr. 178 to Pr. 189 (input terminal function selection) to assign
the function.
The second (third) function has the following applications:
● Switching between normal use and emergency use.
● Switching between heavy load and light load.
● Changing of acceleration/deceleration time by broken line acceleration/deceleration.
● Switching of characteristic between main motor and sub motor.
Second functions selection
6 - 292
Initial
Setting
Description
Value
Range
Second (third) function is immediately
0
made valid with on of the RT(X9) signal.
0
Second (third) function is valid only dur-
ing the RT (X9) signal is on and constant
10
speed operation. (invalid during accelera-
tion/deceleration)
Inverter
Start
High speed
Middle speed
Pr. 155 = 0
Acceleration time
is reflected
Parameters referred to
178–189
Fig. 6-125:
Second functions connection diagram
Fig. 6-126:
Second acceleration/deceleration time
example
Parameter
Refer to
Section
Input terminal
6.14.1
function
selection
I001145C
I001146E