Control mode
6.2.2

Change the control method (Pr. 80, Pr. 81, Pr. 451, Pr. 800)

Set when selecting the advanced magnetic flux vector control, real sensorless vector control or
vector control. Select a control mode from speed control mode, torque control mode and posi-
tion control mode under real sensorless vector control or vector control. The initial value is V/f
control.
● Select a control method using Pr. 800 (Pr. 451) "Control method selection".
● Each control method can be switched using a method switching signal (MC).
Pr.
Name
No.
80
Motor capacity
Number of motor
81
poles
Control method
800
selection
Second motor control
451
method selection
Setting of the motor capacity and the number of motor poles (Pr. 80, Pr. 81 )
● Motor specifications(the motor capacity and the number of motor poles) must be set to select
advanced magnetic flux vector control, real sensorless vector control or vector control.
● Set the motor capacity (kW) in Pr. 80 "Motor capacity" and set the number of motor poles
in Pr. 81 "Number of motor poles".
6 - 70
Initial
Setting Range
Value
01800
0.4–55kW
or less
9999
02160
0–3600kW
or more
9999
2/4/6/8/10
9999
12/14/16/18/20
9999
0–5
9
20
10/11/12
20
10/11/12
20
9999
9999
Description
Set the applied motor capacity.
V/f control
Set the number of motor poles.
Set 10 +
X18 signal-
number of
ON: V/f control
motor poles
V/f control
Vector control
Vector control test operation
Real sensorless vector control
V/f control (advanced mag-
netic flux vector control)
Real sensorless vector control
V/f control (advanced mag-
netic flux vector control)
Second motor is invalid
Parameter
Parameters referred to
Advanced mag-
netic flux vector
control
Real sensorless
vector control,
vector control
(speed control)
Real sensorless
vector control,
vector control
(torque control)
Vector control
(position control)
178–189
Input terminal
function selection
450
Second applied
motor
804
Torque com-
mand source
selection
807
Speed limit selec-
tion
810
Torque limit input
method selec-
tiong
858
Terminal 4 func-
tion assignment
868
Terminal 1 func-
tion assignment
Refer to
Section
6.7.2
6.3
6.4
6.5
6.14.1
6.12.2
6.4.4
6.4.5
6.3.2
6.20.1
6.20.1