Setting the Input Type

3-2

Setting the Input Type

3-2-1

Input Type

Operating Procedure
Operation Level
C
25
0
Initial Setting Level
Input Type
in-t
5
in-t
6
40
The Controller supports four input types: platinum resistance thermometer,
thermocouple, infrared temperature sensor, and analog inputs. Set the input
type that matches the sensor that is used. In the product specifications, there
are models with thermocouple/resistance thermometer inputs (universal
inputs) and models with analog input. The settings differ depending on the
model. Check to make sure which model you are using.
The following example shows how to set a K thermocouple for − 20.0 to
500.0 ° C.
1. Press the O Key for at least three seconds to move from the operation
level to the initial setting level.
2. Press the U Key to enter the set value of the desired sensor.
When you use a K thermocouple ( − 20.0 to 500.0 ° C), enter 6 as the set
value.
Hint: The key operation is saved two seconds after the change, or by press-
ing the O or M Key.
Section 3-2