Setting The Width Of Mv Variation - Omron E5CN User Manual

Digital temperature controllers
Hide thumbs Also See for E5CN:
Table of Contents

Advertisement

Setting the Width of MV Variation

Extraction of
sqrp
Square Root
Low-cut Point
10.0
Operation Level
PV/SP
C
25
100

4-18 Setting the Width of MV Variation

MV Change Rate Limit
MV Change Rate Limit (Heating)
orl
0.0
Parameter name
MV Change Rate
Limit
Operating Procedure
Operation Level
PV/SP
C
25
100
Initial Setting Level
Input Type
in-t
0
PID·ON/OFF
cntl
onof
124
7. Use the U Key to set the parameter to − 10.0.
8. Press the O Key to return to the operation level.
• The MV change rate limit sets the maximum allowable width of change
in the MV per second. If the change in the MV exceeds this setting, the
MV will be changed by the MV change rate limit until the calculated
value is reached. This function is disabled when the setting is 0.0.
• The MV change rate limit does not function in the following situations:
• In manual mode
• During ST execution (Cannot be set when ST is ON.)
• During AT execution
• During ON/OFF control
• While stopped (during MV at Stop output)
• During MV at PV Error output
Setting rage
0.0 to 100.0
This procedure sets the MV change rate limit to 5.0%/s. The related parame-
ters are as follows:
PID·ON/OFF = PID
ST = OFF
1. Press the O Key for at least three seconds to move from the operation
level to the initial setting level.
2. Select the PID ON/OFF parameter by pressing the M Key.
Unit
%/s
0.0
Section 4-18
Default