Advanced Function Setting Level
inf
Input Digital Filter
Function
Setting
pvad
Additional PV Display
Function
Setting
• This parameter sets the time constant for the input digital filter. The follow-
ing diagram shows the effect on data after passing through the digital fil-
ter:
PV before passing through filter
A
(Time
constant)
Input digital filter
Setting range
Unit
0.0 to 999.9
Second
This parameter adds a display at the beginning of the operation level for the
process value (PV). If there is no need to display the set point, use this to dis-
play only the present temperature.
Set to ON to display, and OFF to not display.
Setting range
on: Displayed, off: Not displayed
PV after passing through filter
0.63 A
Time
Default
0.0
Default
off
Section 5-8
207