Advanced Function Setting Level
rest
Standby Sequence Reset
Function
Setting
See
See
202
• This parameter selects the conditions for enabling reset after the standby
sequence of the alarm has been canceled.
• Output is turned OFF when switching to the initial setting level, communi-
cations setting level, advanced function setting level, or calibration level.
• Condition A
Control started (including power ON), and set point, alarm value (alarm
value upper/lower limit), or input shift value (upper/lower-limit temperature
input shift value) changed.
• Condition B
Power ON
• The following example shows the reset action when the alarm type is
lower-limit alarm with standby sequence.
Alarm
(after change)
Alarm
Alarm output:
Condition A
Alarm output:
Condition B
Setting range
a: Condition A, b: Condition B
■ Related Parameters
Alarm 1 to 3 type (initial setting level): Page 191 to 193
Alarm 1 to 3 latch (advanced function setting level): Page 208
Alarm 1 to 3 type must be 5, 6, 7, 10,
or 11.
Condition A only
SP change
Condition A
only
a
Section 5-8
Alarm hysteresis
: Standby sequence canceled
: Standby sequence reset
Default