Advanced Function Setting Level
at-g
AT Calculated Gain
at-h
AT Hysteresis
lcma
Limit Cycle MV Amplitude
Function
Setting
Note
See
See
206
• Normally use the default values for these parameters.
• The AT Calculated Gain parameter sets the gain for when PID values are
calculated using AT. When emphasizing response, decrease the set
value. When emphasizing stability, increase the set value.
• The AT Hysteresis parameter sets the hysteresis for limit cycle operation
during autotuning when switching ON and OFF.
• The Limit Cycle MV Amplitude parameter sets the MV amplitude for limit
cycle operation during autotuning.
Parameter name
AT Calculated Gain
AT Hysteresis
Limit Cycle MV
Amplitude
When the temperature unit is ° F, the default is 1.4.
■ Related Parameters
AT execute/cancel (adjustment level): Page 163
Control must be set to 2-PID control.
Setting range
Unit
0.1 to 10.0
---
°C or °F
Universal input:
0.1 to 999.9
Analog input:
%FS
0.01 to 9.99
5.0 to 50.0
%
Section 5-8
Default
0.8
0.8 (See note.)
0.20
20.0