Omron E5CN User Manual page 230

Digital temperature controllers
Hide thumbs Also See for E5CN:
Table of Contents

Advertisement

Advanced Function Setting Level
st-b
ST Stable Range
Function
Setting
See
See
α
alfa
Function
Setting
See
See
• The setting of this parameter determines when ST operates.
This parameter cannot be used when ST is set to OFF.
Setting range
°C or °F
0.1 to 999.9
■ Related Parameters
Input type: Page 184, PID ON/OFF: Page 188, ST: Page 189 (initial setting
level)
• Normally, use the default for this parameter.
• This parameter sets the 2-PID control α constant.
Setting range
0.00 to 1.00
None
■ Related Parameters
PID ON/OFF: Page 188, ST: Page 189 (initial setting level)
ST must be ON and temperature
input, standard control, 2-PID control
must be set.
Unit
Default
15.0
ST must be OFF and 2-PID control
must be set.
Unit
Default
0.65
Section 5-8
205

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5cn-uE5anE5en

Table of Contents