Precautions When Wiring - Omron E5CN User Manual

Digital temperature controllers
Hide thumbs Also See for E5CN:
Table of Contents

Advertisement

Wiring Terminals
E5CN-U
Control output 1
Relay output
(three terminals used)
SPDT, 250 VAC, 3 A
(resistive load)
Voltage output
mA
(for driving SSR)
12 VDC, 21 mA
Current output
DO NOT
4 to 20 mA DC
USE
0 to 20 mA DC
Load: 600 Ω max.
Note
E5AN/EN
Controllers
• 100 to 240 VAC
• 24 VAC/VDC (no polarity)
Control output 1
Relay output
250 VAC, 5A
Input power supply
(resistive load)
Voltage output
(for driving SSR)
12 VDC, 40 mA
Current output
0 to 20 mA DC
4 to 20 mA DC
Load: 600 Ω max.
Auxiliary output 3
Control output 2
Voltage output
(for driving SSR)
12 VDC, 21 mA
Auxiliary output 2
Long-life relay output
250 VAC, 3 A
(resistive load)
Auxiliary output 1
Auxiliary output
1, 2, 3
Relay outputs
250 VAC, 3 A
(resistive load)
2-2-2

Precautions when Wiring

Note
26
Control output 1
A
DO NOT
DO NOT
USE
USE
B
V
B
Analog input
TC/Pt
universal input
For the Wiring Socket, purchase the P2CF-11 or PG3A-11 separately.
1
11
2
12
3
13
Control output 1
4
14
5
15
6
16
7
17
8
18
9
19
10
20
TC/Pt universal input
• Separate input leads and power lines in order to prevent external noise.
• Use AWG24 (cross-sectional area: 0.205 mm
tional area: 2.081 mm
• Use crimp terminals when wiring the terminals.
• Tighten the terminal screws to a torque of 0.74 to 0.90 N·m, except for the
E5CN-U, which is 0.5 N·m.
• Use the following types of crimp terminals for M3.5 screws.
Do not remove the terminal block. Doing so will result in malfunction or failure.
Auxiliary output
250 VAC, 3 A (resistive load)
(Relay outputs)
Auxiliary output 1
Auxiliary output 2
(Control output (cooling side))
Input power supply
• 100 to 240 VAC
• 24 VAC/VDC (no polarity)
Event Inputs
EV2
EV1
CT1/CT2 Control Output 2
External Power Supply
+
+
CT1
Control output 2
External power supply
-
12 VDC, 20 mA
CT2
DO NOT
-
USE
DO NOT
USE
DO NOT
USE
A
DO NOT
DO NOT
USE
USE
mA
B
V
DO NOT
B
USE
Analog input
2
) twisted-pair cable (stripping length: 5 to 6 mm).
7.2 mm max.
7.2 mm max.
Section 2-2
An input error is sent to the
sent to which the alarm 1
function is assigned.
Option Units
Communications
E53-EN01
E53-EN03
E53-AKB
RS-232C
RS-485
Event inputs
SD
B (+)
11
11
11
RD
12
12
12
SG
DO NOT USE
13
13
13
A heater burnout alarm, heater short alarm,
heater overcurrent alarm, or input alarm is
sent to the output to which the alarm 1
function is assigned.
2
) to AWG14 (cross-sec-
EV2
EV
CT1/CT2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5cn-uE5anE5en