Calibrating Analog Input (Analog Input); Calibrating A Current Input - Omron E5CN User Manual

Digital temperature controllers
Hide thumbs Also See for E5CN:
Table of Contents

Advertisement

Calibrating Analog Input (Analog Input)

t-54
b9a5
t--6
2988
str
no
6-6

Calibrating Analog Input (Analog Input)

6-6-1

Calibrating a Current Input

246
5. When the M Key is pressed, the status changes as shown to the left.
The No. 2 display at this time shows the currently entered count value in
hexadecimal. Set the STV to 54 mV.
Allow the count value on the No. 2 display to fully stabilize, then press the
D Key to temporarily register the calibration settings.
If this count value is outside of the specified range, the No. 2 display will
flash and the count value will not be temporarily registered.
6. When the M Key is pressed, the status changes as shown to the left.
Set the STV to − 6 mV.
Allow the count value on the No. 2 display to fully stabilize, then press the
D Key to temporarily register the calibration settings.
If this count value is outside of the specified range, the No. 2 display will
flash and the count value will not be temporarily registered.
7. When the M Key is pressed, the status changes as shown to the left.
The data to be temporarily registered is not displayed if it is not complete.
Press the U Key. The No. 2 display changes to yes. Release the key and
wait two seconds or press the M Key. This stores the temporarily regis-
tered calibration data to EEPROM.
To cancel the saving of temporarily registered calibration data to EE-
PROM, press the M Key (while no is displayed in the No. 2 display) with-
out pressing the U Key.
8. The calibration mode is ended by turning the power OFF.
In this example, calibration is shown for a Controller with an Analog Input, with
a current input set as the input type.
1,2,3... 1. Connect the power supply.
2. Connect an STV and DMM to the current input terminals, as shown in the
following diagram.
E5CN
Input power supply
STV
DMM
E5CN-U
Input power supply
STV
DMM
3. Turn the power ON.
E5AN/EN
9
Input power supply
10
4
STV
+
5
DMM
10
11
2
+
1
Section 6-6
1
2
19
+