Using The Transfer Output; Transfer Output Function - Omron E5CN User Manual

Digital temperature controllers
Hide thumbs Also See for E5CN:
Table of Contents

Advertisement

Using the Transfer Output

Advanced Function Setting Level
Parameter
init
Initialization
off
Advanced Function Setting Level
Auto/Manual
amad
Select Addition
off
amad
on
pf
a-m
Initial Setting Level
Input Type
in-t
5
Manual Control Level
PV/MV
C
25
0.0
C
25
50.0
Operation Level
C
25
alm
100

4-14 Using the Transfer Output

4-14-1 Transfer Output Function

112
4. Press the D Key to enter the password ( − 169), and move from the initial
setting level to the advanced function setting level.
5. Select the Auto/Manual Select Addition parameter by pressing the M
Key.
6. Use the U Key to set the parameter to ON.
7. Press the M Key to select the PF Setting parameter and confirm that it is
set to "A-M." ("A-M" is the default setting.)
8. Press the O Key for at least one second to move from the advanced
function setting level to the initial setting level.
9. Press the O Key for at least one second to move from the initial setting
level to the operation level.
10. Press the PF Key for at least one second to move from the operation level
to the manual control level.
11. Press the U or D Key to set the manual MV. (In this example, the MV is
set to 50.0%.)
Note
The manual MV setting must be saved (see page 15), but values
changed with key operations are reflected in the control output
immediately.
12. Press the PF Key to move from the manual control level to the operation
level.
• To use a transfer output, change the setting for the Transfer Type parame-
ter to anything other than OFF. (This will enable the Transfer Output Upper
Limit and Transfer Output Lower Limit parameters.)
Section 4-14