Using Heater Burnout, Heater Short, and Heater Overcurrent Alarms
Advanced Function Setting Level
Move to the
init
Advanced
Function
off
Setting Level
Heater
ocu
Overcurrent
Use
on
Operation Level
PV/SP
C
25
100
Adjustment Level
Adjustment Level
l.adj
Display
Heater Current
ct1
1 Value Monitor
0.0
Heater
oc1
Overcurrent
Detection 1
50.0
oc1
20.0
The top parameter in the advanced function setting level is displayed.
4. Press the M Key to select the Heater Overcurrent Use parameter.
Check that this parameter is set to ON (the default), and then set the
Heater Overcurrent Detection 1 parameter.
Setting Heater Overcurrent Detection
5. Press the O Key for at least one second to move from the advanced
function setting level to the initial setting level. Press the O key again for
at least one second to move to the operation level.
6. Press the O Key for less than one second to move from the operation
level to the adjustment level.
7. Press the M Key to select the Heater Current 1 Value Monitor parameter.
Check the current value, and then set the Heater Overcurrent Detection
parameter.
8. Press the M Key to select the Heater Overcurrent Detection 1 parameter.
Refer to Calculating Detection Current Values on page 63 when setting
the values.
9. For this example, set 20.0. To return to the operation level, press the O
Key for less than one second.