Advanced Function Setting Level
sub2
Auxiliary Output 2 Assignment
Function
See
See
222
• This parameter sets the function to be assigned to auxiliary output 2.
none: No function is assigned to auxiliary output 2.
o:
Heating control output is output.
c-o:
Cooling control output is output. (See note 1.)
alm1: Alarm 1 is output.
alm2: Alarm 2 is output.
alm3: Alarm 3 is output.
p.end: Program end is output. (See note 2.)
ralm: Control output ON/OFF count alarm
wr1:
Work bit 1 (See note 4.)
wr2:
Work bit 2 (See note 4.)
wr3:
Work bit 3 (See note 4.)
wr4:
Work bit 4 (See note 4.)
wr5:
Work bit 5 (See note 4.)
wr6:
Work bit 6 (See note 4.)
wr7:
Work bit 7 (See note 4.)
wr8:
Work bit 8 (See note 4.)
(1) If c-o is assigned for standard control, a value equivalent to 0% will be
Note
output.
(2) Can be selected when the Program Pattern parameter is set to OFF, but
the function will be disabled.
(3) If the Standard or Heating/Cooling parameter is set to heating/cooling
control when there is no control output 2 (E5CN/CN-U), control automat-
ically switches to c-o.
(4) WR1 to WR8 are not displayed when the logic operation function is not
used.
■ Related Parameters
Standard or heating/cooling: Page 188, Program pattern: Page 189, (initial
setting level)
Auxiliary output 2 must be assigned.
Setting range
Section 5-8
Default
alm2
(See note
3.)