Executing Heating/Cooling Control

Operating Procedure
Initial Setting Level
Input Type
in-t
0
Scaling Upper
in-h
Limit
100
in-h
950
Scaling Lower
in-l
Limit
0
in-l
100
Decimal Point
dp
0
dp
1
4-4

Executing Heating/Cooling Control

4-4-1

Heating/Cooling Control

Display
(humidity)
Upper limit (95.0%)
Lower limit (10.0%)
4
In this example scaling is set to display 4 to 20 mA as 10.0% to 95.0%.
1. Press the O Key for three seconds to move from the operation level to
the initial setting level.
2. Select Scaling Upper Limit parameter by pressing the M Key.
3. Use the U and D Keys to set the parameter to 950.
4. Select the Scaling Lower Limit parameter by pressing the M Key.
5. Press the U and D Keys to set 100.
6. Select the Decimal Point parameter by pressing the M Key.
7. Press the U and D Keys to set 1.
8. To return to the operation level, press the O Key for one second.
Heating/cooling control can be used on the E5CN-@M@-500 (with an E53-
CNQ@@N2), E5CN-@2M@-500, E5AN-@3@M@-500-N or E5EN-@3@M@-
500-N. Heating/cooling control operates when h-c (heating/cooling) is
selected for the Standard or Heating/Cooling parameter.
Input (mA)
20
Section 4-4
83