Setting The Input Type; Input Type - Omron E5CC User Manual

Digital
Hide thumbs Also See for E5CC:
Table of Contents

Advertisement

4-3

Setting the Input Type

The Controller supports four input types: resistance thermometer, thermocouple, infrared temperature
sensor, and analog inputs. Set the input type that matches the sensor that is used.
4-3-1

Input Type

The following example shows how to set a K thermocouple for −20.0 to
500.0°C (input type 6).
Operating Procedure
1
Press the O Key for at least 3 seconds to move from the
Operation Level to the Initial Setting Level. The in-t (Input
Type) parameter will be displayed.
2
Press the U or D Key to select 6 (K thermocouple at −20.0 to
500.0°C).
The default is 5 (5: K thermocouple at −200 to 1,300°C).
Additional Information
Changes that are made with key operations are applied when the O or M Key is pressed. They
are also applied if you do nothing for 3 seconds or longer.
E5@C Digital Temperature Controllers User's Manual (H174)
4 Basic Operation
Initial Setting Level
in-t
Input Type
5
in-t
6
4 - 11
4

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5acE5ec

Table of Contents