Advertisement

Logic Operations
(2) Turns ON when either the control output 1 or 2 ON/OFF count alarm is
ON.
5. Switching between Normally Open and Normally Closed for Inputs A to D
Click the condition to switch between normally open and normally closed
inputs A to D.
Normally open
6. Switching between Normally Open and Normally Closed for Work Bits
Click the condition to switch between normally open and normally closed
work bits.
Normally open
7. Setting ON Delay Times
When an input with ON delay turns ON, the output will turn ON after the
set delay time has elapsed. The setting range is 0 to 9,999. The default is
0 (disabled).
8. Setting OFF Delay Times
When an input with OFF delay turns OFF, the output will turn OFF after the
set delay time has elapsed. The setting range is 0 to 9,999. The default is
0 (disabled).
9. Switching ON/OFF Delay Time Unit
Select either seconds or minutes for the ON/OFF delay time unit. The de-
fault is seconds.
10. Selecting the Number of Multi-SP Uses
Select the number of Multi-SP uses from 0 to 2.
11. Changing Event Input Data
Select the event input conditions from the following setting ranges.
Parameter name
Event Input Data 1
Event Input Data 2
Event Input Data 3
Event Input Data 4
Normally closed
Normally closed
Setting range
0: Not assigned.
1: Event input 1 (external input)
2: Event input 2 (external input)
3: Event input 3 (external input)
4: Event input 4 (external input)
5: Work bit 1
6: Work bit 2
7: Work bit 3
8: Work bit 4
9: Work bit 5
10: Work bit 6
11: Work bit 7
12: Work bit 8
Same as for event input data 1
Same as for event input data 1
Same as for event input data 1
Section 4-22
137