Setting the Input Type

3-2

Setting the Input Type

3-2-1

Input Type

Operating Procedure
Operation Level
C
25
0
Initial Setting Level
Input type
in-t
5
in-t
6
36
The Controller supports four input types: platinum resistance thermometer,
thermocouple, infrared temperature sensor, and analog inputs. Set the input
type that matches the sensor that is used. In the product specifications, there
are models with thermocouple/resistance thermometer inputs (multi-input)
and models with analog input. The settings differ depending on the model.
Check to make sure which model you are using.
The following example shows how to set a K thermocouple for
500.0 C.
1. Press the O key for at least three seconds to move from the operation
level to the initial setting level.
2. Press the U key to enter the set value of the desired sensor.
When you use a K thermocouple ( 20.0 to 500.0 C), enter 6 as the set
value.
Hint: The key operation is fixed two seconds after the change, or by press-
ing the O or M key.
Section 3-2
20.0 to