Omron E5CN User Manual page 148

Digital temperature controllers
Hide thumbs Also See for E5CN:
Table of Contents

Advertisement

Using the Extraction of Square Root Parameter
Parameter name
Extraction of Square
Root Enable
Extraction of Square
Root Low-cut Point
Operating Procedure
Operation Level
PV/SP
C
25
100
Initial Setting Level
Input Type
in-t
0
Extraction
sqr
of Square
Root Enable
off
Extraction
sqr
of Square
Root Enable
on
Operation Level
PV/SP
C
25
100
Adjustment Level
l.adj
Extraction of
sqrp
Square Root
Low-cut Point
0.0
Extraction of
square root
100% FS
Extraction of square
root low-cut point
0
Argument 1 (Input Data)
Setting rage
OFF: Disabled, ON: Enabled
0.0 to 100.0
This procedure sets the Extraction of Square Root Low-cut Point parameter to
10.0%.
1. Press the O Key for at least three seconds to move from the operation
level to the initial setting level.
2. Press the M Key to select the Extraction of Square Root Enable param-
eter.
3. Use the U Key to select ON.
4. Press the O Key for at least one second to move from the initial setting
level to the operation level.
5. Press the O Key to move from the operation level to the adjustment level.
6. Select the Extraction of Square Root Low-cut Point parameter by press-
ing the M Key.
100% FS
Unit
---
OFF
%
0.0
Section 4-17
Default
123

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5cn-uE5anE5en

Table of Contents