6— Configuration - Configuration Overview
What to configure
Table 17 summarizes the parameters that are included in the configuration database for a ST 3000 pressure
transmitter.

Table 17 Summary of Pressure Transmitter Configuration Parameters

Configuration Data
Tag
(Transmitter Tag Number)
PV unit
(Unit of Measurement)
Range Values
PV LRV
(Lower Range Value)
Process input for
4 mA (0%) output
PV URV
(Upper Range Value)
Process input for
20 mA (100%) output
Local meter
48
Key in a tag identification up to eight characters in length.
Select any one of the pre-programmed engineering units.
ST 3000 transmitters with inches of water ranges are factory
calibrated using pressure referenced to a temperature of 39.2°F
(4°C).
Pressure readings can be displayed in any one of these pre-
programmed engineering units:
inH2O
inHg
ftH2O
mmH2O
mmHg
psi
Key in desired value through communicator keyboard or set LRV to
applied pressure.
Key in desired value through communicator keyboard or set URV to
applied pressure.
Setup parameters for integral smart meter display.
Installed
(Read only – detects if meter is installed in transmitter)
Units
(Engineering units for meter display)
Upper
(Upper display limit, if applicable)
Lower
(Lower display limit, if applicable)
ST 3000 HART Transmitter Release 300 User Manual
Setting or Selection
bar
torr
mbar
atm
g/Sq cm
MPa
kg/Sq cm
inH2O @ 4degC
Pa
mmH2O @ 4degC
kPa
inH2O @ 60degF
Table continued on next page ⇒